Input wiring
Single-phase three-wire
Rated voltage
208 / 220 / 230 / 240 Vac
Voltage range
110 - 176 Vac (linear derating between 50% and 100% load), 176 - 288 Vac (no derating)
Rated frequency
50 / 60 Hz (auto-sensing)
Frequency range
40 - 70 Hz (auto-sense)
Power factor
>= 0.99
Bypass voltage range
(- 40%, +15%) (settable)Total Harmonic Distortion (THDi) <= 5%
Output wiring
Single-phase three-wire
Voltage rated
208 (PF=0.9) / 220 / 230 / 240 Vac
Voltage regulation
1 +-
Frequency
Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode
Waveform
Sinusoidal
Power factor
1
Total harmonic distortion (THDv)
<= 1% (linear load, <= 4% (non-linear load)
Crest factor
3:1
Overload
105% - 110% for 10 min, 110% - 125% for 1 min,126% - 150% for 30 s
DC voltage
192 Vdc (192 - 240 Vdc settable)
Number of battery
16 - 20
Inbuilt battery (standard model)
12 V / 7 Ah x 16
Charging current
1A
Recharge time
Standard model: 90% capacity restored in 8 hours
Efficiency
>= 94% at 100% load, max. 95% at 60% load, >= 98% in ECO mode
Transfer time
0 ms
Protections
Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Max. number of parallel connections
4
Communications
RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
Display
LCD + LED
Operating temperature
0 - 40°C
Storage temperature
from -25 to 55 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000 m, derating 1% for each additional 100 m
IP rating
IP 20
Noise level at 1m
<= 55 Db
Dimensions
191 x 465 x 711
Packaged dimensions
310 x 654 x 941
Net weight (kg)
53
Gross weight (kg)
61

Αναμένεται
Κωδικός
0.502.049
Κατηγορία
Tescom UPS
Input wiring
Single-phase three-wire
Rated voltage
208 / 220 / 230 / 240 Vac
Voltage range
80 - 176 Vac (linear derating between 40% and 100% load), 176 - 288 Vac (no derating)
Rated frequency
50 / 60 Hz (auto-sensing)
Frequency range
40 - 70 Hz
Power factor
>= 0.99
Bypass voltage range
(- 40%, +15%) (settable)Total Harmonic Distortion (THDi) <= 5%
Output wiring
Single-phase
Voltage rated
208 (PF=0.9) / 220 / 230 / 240 Vac
Voltage regulation
1 +-
Frequency
Synchronized to bypass in mains mode, 50 / 60 Hz+ - 0.1% Hz in battery mode
Waveform
Sinusoidal
Power factor
1
Total harmonic distortion (THDv)
<= 1% (linear load), <= 3% (non-linear load)
Crest factor
3:01
Overload
102% - 110% for 10 min, 110% - 125% for 1 min,125% - 150% for 30 s
DC voltage
192 Vdc (192 - 240 Vdc settable) AGM VRLA and Li-On (optional)
Number of battery
16 pcs (16 ~ 20 settable)
Inbuilt battery (standard model)
(sold separately)
Charging current
12A
Recharge time
depend on the capacity of battery
Efficiency
>= 94% at 100% load, max. 94.5% at 60% load, >= 98% in ECO mode
Transfer time
0 ms
Protections
Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Max. number of parallel connections
4
Communications
RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
Display
LCD + LED
Operating temperature
0 - 40°C
Storage temperature
from -25 to 55 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000 m, derating 1% for each additional 100 m
IP rating
IP 20
Noise level at 1m
<= 55 dB
Dimensions
440 x 580 x 88
Packaged dimensions
514 x 696 x 168
Net weight (kg)
12
Gross weight (kg)
14

Αναμένεται
Κωδικός
0.502.120
Κατηγορία
Tescom UPS
Nominal Voltage
200/208/220/230/240 VAC
Voltage range
10~300VAC ± 3 % at 50% load 176~300VAC ± 3 % at 100% load
Frequency range
46~54 Hz 50Hz / 56~64 Hz 60HzPhase Single phase with ground
Power factor
>= 0.99 full loadTotal Harmonic Distortion (THDi) <4% 100% Load, <6% 50% Load
Output Voltage
200*/208*/220/230/240 VAC
AC Voltage Regulation
= +- 1%
Frequency Range
46~54 Hz 50 Hz / 56~64 Hz 60 Hz
Current Crest Ratio
3:1 max
Harmonic Distortion
<=1% THD (Linear Load), <= 4 % THD (Non-linear Load)
Transfer Time
AC mode to Battery mode= Zero, Inverter to Bypass= Zero
Waveform
Pure Sinewave
Overload
AC Mod 100%~110%: 10min / 110%~130%: 1min / >130% : 1sec, Battery Mode 100%~110%: 30sec / 110%~130%: 10sec / >130% : 1sec
AC Mode
94%
ECO Mode
98,50%
Battery Mode
92%
Battery Type (VRLA)
Depending on applications
Numbers
16-20**
Typical Recharge Time
9 hours recover to 90% capacity
Charging Current
4.0 A
Charging Voltage
(13.65VDC x battery number) +- 1%
Standard Model Dimension, D x W x H (mm)
610 x 438 x 88 [2U]
Net Weight
17 kg
Humidity
<95 % RH @ 0- 40 (non-condensing)
Noise Level
Less than 58dB 1 Meter
Smart RS-232/USB & Softwarel
Supports Windows? 2000/ 2003/ XP/ Vista / 2008, Windows 7/8, Linux, Unix, and MAC
Optional SNMPl
Power management from SNMP manager and web browser
EMC/safety
EMC EN62040-2 C2 / EN 62040 - 1 / EN 62040 3 / RoHS 2

Αναμένεται
Κωδικός
0.502.119
Κατηγορία
Tescom UPS
Nominal Voltage
200/208/220/230/240 VAC
Voltage range
10~300VAC ± 3 % at 50% load 176~300VAC ± 3 % at 100% load
Frequency range
46~54 Hz 50Hz / 56~64 Hz 60HzPhase Single phase with ground
Power factor
>= 0.99 full loadTotal Harmonic Distortion (THDi) <4% 100% Load, <6% 50% Load
Output Voltage
200*/208*/220/230/240 VAC
AC Voltage Regulation
= +- 1%
Frequency Range
46~54 Hz 50 Hz / 56~64 Hz 60 Hz
Current Crest Ratio
3:1 max
Harmonic Distortion
<=1% THD (Linear Load), <= 4 % THD (Non-linear Load)
Transfer Time
AC mode to Battery mode= Zero, Inverter to Bypass= Zero
Waveform
Pure Sinewave
Overload
AC Mod 100%~110%: 10min / 110%~130%: 1min / >130% : 1sec, Battery Mode 100%~110%: 30sec / 110%~130%: 10sec / >130% : 1sec
AC Mode
94%
ECO Mode
98,50%
Battery Mode
92%
Battery Type (VRLA)
Depending on applications
Numbers
16-20**
Typical Recharge Time
9 hours recover to 90% capacity
Charging Current
4.0 A
Charging Voltage
(13.65VDC x battery number) +- 1%
Standard Model Dimension, D x W x H (mm)
610 x 438 x 88 [2U]
Net Weight
17 kg
Humidity
<95 % RH 0- 40 (non-condensing)
Noise Level
Less than 55dBA 1 Meter
Smart RS-232/USB & Softwarel
Supports Windows 2000/ 2003/ XP/ Vista / 2008, Windows 7/8, Linux, Unix, and MAC
Optional SNMPl
Power management from SNMP manager and web browser
EMC/safety
EMC EN62040-2 C2 / EN 62040 - 1 / EN 62040 3 / RoHS 2

Αναμένεται
Κωδικός
0.502.121
Κατηγορία
Tescom UPS
Nomina voltage
200/208/220/230/240 VAC
Voltage range
110-300 VAC +- 5% , 50% load, 160-300 VAC +-5% ,100% load
Frequency
40Hz - 70Hz
Power factor
>=0.99 @ nominal voltage (100% load)
Harmonic Distortion(THDi)
<= 5% @ nominal input voltage
Output Voltage
200*/208*/220/230/240 VAC
Voltage regulation
1 +-
Frequency (Synchronized Range)
57 - 63 Hz or 47 - 53 Hz
Frequency Range (Batt. Mode)
50 Hz +- 0.1Hz or 60Hz +- 0.1Hz
Waveform
4 sm
Power factor
0.9
Total harmonic distortion
= 2 % THD (Linear Load), = 4 % THD (Non-linear load)
Current Crest Ratio
3:1 (max.)
Overload
110-130% : 5 min / 130-140%: 30 sec / >140% : 1.5 sec to 100ms
Outlets
8 x IEC 320 C13
Battery Type (VRLA)
2 x 12 V / 9 AH
Typical Recharge Time
3 hours recover to 95% capacity for internal battery 2A charging current
Charging current (max.)
1A
Charging Current
Default 2A, max. 12A adjustable
Charging Voltage
27.4 VDC +- 1%
Dimension
410 x 438 x 88
Net Weight (without battery) (kgs)
6,6
Net Weight (w/built-int battery) (kgs)
11,6
Humidity
5-95 % RH , 0- 40°C (non-condensing)
Noise Level
Less than 50dBA @ 1 Meter
Altitude
10% de-rating for over 1000m (The altitude should not exceed 3000m)
Smart RS-232/USB & Software
Supports Windows 2000/2003/ XP/ Vista/ 2008/ 7/ 8, Linux and MAC
Optional SNMP
Power management from SNMP manager and web browser
EMC/safety
EMC EN62040-2 C2 / EN 62040 - 1 / EN 62040 3 / RoHS 2
Βρέθηκαν 29 προϊόντα
Προϊόντα 1 - 5 από 29
Οι τιμές ΔΕΝ περιλαμβάνουν τον Φ.Π.Α.
Οι Πιστοποιήσεις μας
Γιατί Ξεχωρίζουμε
ΠΕΡΙΣΣΟΤΕΡΑ
Microsoft authorized refurbisher
Microsoft surface authorized reseller
ADISA Accredited Pass
BLANCO
WEEE
ISO 27001
ISO 14001
ISO 9001
×

Αυτός ο ιστότοπος χρησιμοποιεί cookies για τη διάκριση των επισκεπτών. Για να αποδεχθείτε την τοποθέτηση cookies, επιλέξτε
Πολιτική cookies