INPUT
Rated voltage 208 V / 220 V / 230 V / 240 Vac
Voltage range 110 - 176 Vac (linear derating between 50% and 100% load ), 176 - 280 Vac (no derating), 280 - 300 Vac (derating 50%)
Frequency 50/60 Hz± 5 Hz (auto-sensing)
Power factor >= 0.99
Bypass voltage range - 40% +20% (settable)Total Harmonic Distortion (THDi) <=5%
OUTPUT
Voltage 208 V / 220 V / 230 V / 240 Vac (settable via LCD)
Voltage regulation ±1%
Frequency 45 - 55 Hz or 55 - 65 Hz (synchronized range), 50 / 60 Hz± 0.1 Hz (battery mode)
Waveform Sinusoidal
Power factor 1.0
Total Harmonic distortion (THDv) <= 2% (linear load); <= 5% (non-linear load)
Crest factor 3:01
Overload 105% -110% for 30 min, 110% - 130% for 10 min, 130% - 150% for 30s, > 150% for 500 ms
BATTERIES
Battery type Sealed lead acid maintenance free battery
DC voltage 24 V (XL)
Inbuilt battery 2 x 9 Ah
Charging current (max.)Long time model (XL): 12 A
Recharge time Long time model: depend on the capacity of battery
SYSTEM
Mains Efficiency Mains mode: >= 93.5%, Battery mode: >= 89.2%, ECO mode: >= 97.5%
Transfer time Mains mode to battery mode: Oms Inverter mode to bypass mode: 4 ms (typical)
Protections Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection
Communication port RS232 (standard), USB / RS485 / SNMP/ dry contacts (optional)
Display LCD
ENVIRONMENT
Operating humidity 0- 95% RH @ 0- 40°C (non-condensing)
Storage temperature -25°C - 55°C (exclude batteries)
Operating altitude 0 - 95% (non-condensing)
Altitude <= 1000m, above 1000m, derating 1% for each additional 100 m
IP rating IP20
Noise level at 1m <= 50 dB
Dimensions (W × D × H) (mm) 440x338x88
Packaged dimensions 545x428x194
Net weight10.92kg