THESSALONIKI2310586150
Microsoft Authorized Refurbisher Microsoft surface authorized reseller

UPS

UPS (Uninterruptible Power Supply) is the device, which supplies electricity to other devices, in the event of a power cut. It acts as a large battery that interferes between our devices (PC, modem router, wireless phone, etc.) and the power supply network.

In the event of a power failure, our devices may be damaged as a result of a sudden power failure. So UPS enables us to keep our devices running and then shut them down properly. By using UPS, we protect our devices and we also have the ability to operate them during a power cut, whilst securely shutting down any open programs to avoid data loss.

Alfanet’s refurbished UPS, consist only of the finest business series of the most important brands in the market, HP, APC, EATON hence offering to our customers superior functionality equipment, in full compliance with the international remanufacturing standards of MAR (Microsoft authorized Refurbisher), ADISA, ISO 9001 & ISO 14001.

When you buy refurbished UPS from Alfanet A.E., you acquire a business spec equipment at an incomparably lower price than the new ones and with a 2-year warranty for the device and 6 months for the batteries. At the same time, you save money, you contribute to the environment, by promoting recycling and reducing electronic waste.

Limited items
Code
0.081.111
Category
Spare Parts

Limited items
Code
0.081.098
Category
Batteries

Limited items
Code
0.081.141
Category
Various UPS Tower

Limited items
Code
1.080.052
Category
HP Compaq Rack

Is expected
Code
0.502.121
Category
Tescom UPS
Nomina voltage
200/208/220/230/240 VAC
Voltage range
110-300 VAC +- 5% , 50% load, 160-300 VAC +-5% ,100% load
Frequency
40Hz - 70Hz
Power factor
>=0.99 @ nominal voltage (100% load)
Harmonic Distortion(THDi)
<= 5% @ nominal input voltage
Output Voltage
200*/208*/220/230/240 VAC
Voltage regulation
1 +-
Frequency (Synchronized Range)
57 - 63 Hz or 47 - 53 Hz
Frequency Range (Batt. Mode)
50 Hz +- 0.1Hz or 60Hz +- 0.1Hz
Waveform
4 sm
Power factor
0.9
Total harmonic distortion
= 2 % THD (Linear Load), = 4 % THD (Non-linear load)
Current Crest Ratio
3:1 (max.)
Overload
110-130% : 5 min / 130-140%: 30 sec / >140% : 1.5 sec to 100ms
Outlets
8 x IEC 320 C13
Battery Type (VRLA)
2 x 12 V / 9 AH
Typical Recharge Time
3 hours recover to 95% capacity for internal battery 2A charging current
Charging current (max.)
1A
Charging Current
Default 2A, max. 12A adjustable
Charging Voltage
27.4 VDC +- 1%
Dimension
410 x 438 x 88
Net Weight (without battery) (kgs)
6,6
Net Weight (w/built-int battery) (kgs)
11,6
Humidity
5-95 % RH , 0- 40°C (non-condensing)
Noise Level
Less than 50dBA @ 1 Meter
Altitude
10% de-rating for over 1000m (The altitude should not exceed 3000m)
Smart RS-232/USB & Software
Supports Windows 2000/2003/ XP/ Vista/ 2008/ 7/ 8, Linux and MAC
Optional SNMP
Power management from SNMP manager and web browser
EMC/safety
EMC EN62040-2 C2 / EN 62040 - 1 / EN 62040 3 / RoHS 2

Is expected
Code
0.502.046
Category
Tescom UPS
Input wiring
Single-phase three-wire
Rated voltage
208 / 220 / 230 / 240 Vac
Voltage range
110 - 176 Vac (linear derating between 50% and 100% load), 176 - 288 Vac (no derating)
Rated frequency
50 / 60 Hz (auto-sensing)
Frequency range
40 - 70 Hz (auto-sense)
Power factor
>= 0.99
Bypass voltage range
(- 40%, +15%) (settable)Total Harmonic Distortion (THDi) <= 5%
Output wiring
Single-phase three-wire
Voltage rated
208 (PF=0.9) / 220 / 230 / 240 Vac
Voltage regulation
1 +-
Frequency
Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode
Waveform
Sinusoidal
Power factor
1
Total harmonic distortion (THDv)
<= 1% (linear load, <= 4% (non-linear load)
Crest factor
3:1
Overload
105% - 110% for 10 min, 110% - 125% for 1 min,126% - 150% for 30 s
DC voltage
192 Vdc (192 - 240 Vdc settable)
Number of battery
16 - 20
Inbuilt battery (standard model)
12 V / 7 Ah x 16
Charging current
1A
Recharge time
Standard model: 90% capacity restored in 8 hours
Efficiency
>= 94% at 100% load, max. 95% at 60% load, >= 98% in ECO mode
Transfer time
0 ms
Protections
Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Max. number of parallel connections
4
Communications
RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
Display
LCD + LED
Operating temperature
0 - 40°C
Storage temperature
from -25 to 55 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000 m, derating 1% for each additional 100 m
IP rating
IP 20
Noise level at 1m
<= 55 Db
Dimensions
191 x 465 x 711
Packaged dimensions
310 x 654 x 941
Net weight (kg)
53
Gross weight (kg)
61

Is expected
Code
0.502.049
Category
Tescom UPS
Input wiring
Single-phase three-wire
Rated voltage
208 / 220 / 230 / 240 Vac
Voltage range
80 - 176 Vac (linear derating between 40% and 100% load), 176 - 288 Vac (no derating)
Rated frequency
50 / 60 Hz (auto-sensing)
Frequency range
40 - 70 Hz
Power factor
>= 0.99
Bypass voltage range
(- 40%, +15%) (settable)Total Harmonic Distortion (THDi) <= 5%
Output wiring
Single-phase
Voltage rated
208 (PF=0.9) / 220 / 230 / 240 Vac
Voltage regulation
1 +-
Frequency
Synchronized to bypass in mains mode, 50 / 60 Hz+ - 0.1% Hz in battery mode
Waveform
Sinusoidal
Power factor
1
Total harmonic distortion (THDv)
<= 1% (linear load), <= 3% (non-linear load)
Crest factor
3:01
Overload
102% - 110% for 10 min, 110% - 125% for 1 min,125% - 150% for 30 s
DC voltage
192 Vdc (192 - 240 Vdc settable) AGM VRLA and Li-On (optional)
Number of battery
16 pcs (16 ~ 20 settable)
Inbuilt battery (standard model)
(sold separately)
Charging current
12A
Recharge time
depend on the capacity of battery
Efficiency
>= 94% at 100% load, max. 94.5% at 60% load, >= 98% in ECO mode
Transfer time
0 ms
Protections
Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Max. number of parallel connections
4
Communications
RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
Display
LCD + LED
Operating temperature
0 - 40°C
Storage temperature
from -25 to 55 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000 m, derating 1% for each additional 100 m
IP rating
IP 20
Noise level at 1m
<= 55 dB
Dimensions
440 x 580 x 88
Packaged dimensions
514 x 696 x 168
Net weight (kg)
12
Gross weight (kg)
14

Is expected
Code
0.502.050
Category
Tescom UPS
Input wiring
Single-phase three-wire
Rated voltage
208 / 220 / 230 / 240 Vac
Voltage range
80 - 176 Vac (linear derating between 40% and 100% load), 176 - 288 Vac (no derating)
Rated frequency
50 / 60 Hz (auto-sensing)
Frequency range
40 - 70 Hz
Power factor
>= 0.99
Bypass voltage range
(- 40%, +15%) (settable)Total Harmonic Distortion (THDi) <= 5%
Output wiring
Single-phase
Voltage rated
208 (PF=0.9) / 220 / 230 / 240 Vac
Voltage regulation
1 +-
Frequency
Synchronized to bypass in mains mode, 50 / 60 Hz+ - 0.1% Hz in battery mode
Waveform
Sinusoidal
Power factor
1
Total harmonic distortion (THDv)
<= 1% (linear load), <= 3% (non-linear load)
Crest factor
3:01
Overload
102% - 110% for 10 min, 110% - 125% for 1 min,125% - 150% for 30 s
DC voltage
192 Vdc (192 - 240 Vdc settable) AGM VRLA and Li-On (optional)
Number of battery
16 pcs (16 ~ 20 settable)
Inbuilt battery (standard model)
(sold separately)
Charging current
12A
Recharge time
depend on the capacity of battery
Efficiency
>= 94% at 100% load, max. 94.5% at 60% load, >= 98% in ECO mode
Transfer time
0 ms
Protections
Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Max. number of parallel connections
4
Communications
RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
Display
LCD + LED
Operating temperature
0 - 40°C
Storage temperature
from -25 to 55 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000 m, derating 1% for each additional 100 m
IP rating
IP 20
Noise level at 1m
<= 55 dB
Dimensions
440 x 580 x 88
Packaged dimensions
514 x 696 x 168
Net weight (kg)
14
Gross weight (kg)
16

Is expected
Code
0.502.047
Category
Tescom UPS
Input wiring
Single-phase three-wire
Rated voltage
208 / 220 / 230 / 240 Vac
Voltage range
110 - 176 Vac (linear derating between 50% and 100% load), 176 - 288 Vac (no derating)
Rated frequency
50 / 60 Hz (auto-sensing)
Frequency range
40 - 70 Hz (auto-sense)
Power factor
>= 0.99
Bypass voltage range
(- 40%, +15%) (settable)Total Harmonic Distortion (THDi) <= 5%
Output wiring
Single-phase three-wire
Voltage rated
208 (PF=0.9) / 220 / 230 / 240 Vac
Voltage regulation
1 +-
Frequency
Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode
Waveform
Sinusoidal
Power factor
1
Total harmonic distortion (THDv)
<= 1% (linear load, <= 4% (non-linear load)
Crest factor
3:1
Overload
105% - 110% for 10 min, 110% - 125% for 1 min,126% - 150% for 30 s
DC voltage
192 Vdc (192 - 240 Vdc settable)
Number of battery
16 - 20
Inbuilt battery (standard model)
12 V / 7 Ah x 16
Charging current
1A
Recharge time
Standard model: 90% capacity restored in 8 hours
Efficiency
>= 94% at 100% load, max. 95% at 60% load, >= 98% in ECO mode
Transfer time
0 ms
Protections
Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Max. number of parallel connections
4
Communications
RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
Display
LCD + LED
Operating temperature
0 - 40°C
Storage temperature
from -25 to 55 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000 m, derating 1% for each additional 100 m
IP rating
IP 20
Noise level at 1m
<= 55 Db
Dimensions
191 x 465 x 711
Packaged dimensions
310 x 654 x 941
Net weight (kg)
53
Gross weight (kg)
61

Is expected
Code
0.502.048
Category
Tescom UPS
Input wiring
Single-phase three-wire
Rated voltage
208 / 220 / 230 / 240 Vac
Voltage range
110 - 176 Vac (linear derating between 50% and 100% load), 176 - 288 Vac (no derating)
Rated frequency
50 / 60 Hz (auto-sensing)
Frequency range
40 - 70 Hz (auto-sense)
Power factor
>= 0.99
Bypass voltage range
(- 40%, +15%) (settable)Total Harmonic Distortion (THDi) <= 5%
Output wiring
Single-phase three-wire
Voltage rated
208 (PF=0.9) / 220 / 230 / 240 Vac
Voltage regulation
1 +-
Frequency
Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode
Waveform
Sinusoidal
Power factor
1
Total harmonic distortion (THDv)
<= 1% (linear load, <= 4% (non-linear load)
Crest factor
3:1
Overload
105% - 110% for 10 min, 110% - 125% for 1 min,126% - 150% for 30 s
DC voltage
192 Vdc (192 - 240 Vdc settable)
Number of battery
16 - 20
Inbuilt battery (standard model)
12 V / 9 Ah x 16
Charging current
1A
Recharge time
Standard model: 90% capacity restored in 8 hours
Efficiency
>= 94% at 100% load, max. 95% at 60% load, >= 98% in ECO mode
Transfer time
0 ms
Protections
Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Max. number of parallel connections
4
Communications
RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
Display
LCD + LED
Operating temperature
0 - 40°C
Storage temperature
from -25 to 55 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000 m, derating 1% for each additional 100 m
IP rating
IP 20
Noise level at 1m
<= 58 dB
Dimensions
191 x 495 x 711
Packaged dimensions
310 x 685 x 941
Net weight (kg)
62
Gross weight (kg)
70

Is expected
Code
0.502.134
Category
Tescom UPS
Rated Voltage
380 / 400 / 415 Vac (L-L)
Voltage range
304~478Vac (L-L), full load 228V~304Vac (L-L), load decrease linearly according to the min phase voltage
Rated frequency
50 / 60 Hz (auto-sensing)
Frequency range
40 ~ 70 Hz
Power factor
> 0.99Total Harmonic Distortion (THDi) <3% (full linear load)
Rated Voltage
380 / 400 / 415 Vac (L-L)
Voltage Regulation
= +- 1% (full linear load)
Frequency
Synchronized with utility in mains mode, 50/60 Hz ±0.1% in battery mode
Waveform
Sinusoidal
Power factor
1
Harmonic Distortion
<1% (full linear load) <3% (full non-linear load according to IEC/EN62040-3)
Current Crest Ratio
3:1
Overload
<110%, 60min, 110%~125%, 10min; 125%~150%,1min, >150%, 200ms
Bypass voltage range
Selectable, default -20%~+15% Up limited: +10%, +15%, +20%, +25%; Down limited: -10%, -15%, -20%, -30%, -40%
Bypass frequency range
Selectable, + - 1Hz, + - 3Hz, + - 5Hz
Bypass overload
125%: long term operation; 125%~130%: 10min; 130%~150%: 1min; 150%~400%: 1s; >400%, less than 200ms
DC voltage
120 ~ 240 Vdc settable
Charging current
10A Max
Recharge time
90% capacity restored in 8 hours
Charger voltage precision
1%
Inbuilt battery
N/A
Efficiency
95% Max
Transfer time
0 ms
Protections
Short-circuit, output overload, overtemperature, battery low voltage, overvoltage / undervoltage and fan failure
Max. number of parallel connections
4
Communications
RS232, USB, RS485, EPO, Dry contacts, Parallel port (Standard) SNMP card, WI-FI card, GPRS card, SMS alarms (Optional)
Display
LED + 5 inches LCD touch screen
Operating temperature
0C ~ 40C
Storage temperature
Min 40 C Under Zero ~ 70 B360C (B360without battery)
Relative humidity
0 ~ 95% (non-condensing)
Altitude
<1000m, load derated 1% per 100m from 1000 ~ 2000m
IP rating
IP 20
Noise level at 1 m
55dB 100% load, 52dB 50% load
Dimensions (mm)
250 x 720 x 560

Is expected
Code
0.502.136
Category
Tescom UPS
Rated Voltage
380 / 400 / 415 Vac (L-L)
Voltage range
304~478Vac (L-L), full load 228V~304Vac (L-L), load decrease linearly according to the min phase voltage
Rated frequency
50 / 60 Hz (auto-sensing)
Frequency range
40 ~ 70 Hz
Power factor
> 0.99Total Harmonic Distortion (THDi) <3% (full linear load)
Rated Voltage
380 / 400 / 415 Vac (L-L)
Voltage Regulation
= +- 1% (full linear load)
Frequency
Synchronized with utility in mains mode, 50/60 Hz ±0.1% in battery mode
Waveform
Sinusoidal
Power factor
1
Harmonic Distortion
<1% (full linear load) <3% (full non-linear load according to IEC/EN62040-3)
Current Crest Ratio
3:1
Overload
<110%, 60min, 110%~125%, 10min; 125%~150%,1min, >150%, 200ms
Bypass voltage range
Selectable, default -20%~+15% Up limited: +10%, +15%, +20%, +25%; Down limited: -10%, -15%, -20%, -30%, -40%
Bypass frequency range
Selectable, + - 1Hz, + - 3Hz, + - 5Hz
Bypass overload
125%: long term operation; 125%~130%: 10min; 130%~150%: 1min; 150%~400%: 1s; >400%, less than 200ms
DC voltage
120 ~ 240 Vdc settable
Charging current
10A Max
Recharge time
90% capacity restored in 8 hours
Charger voltage precision
1%
Inbuilt battery
N/A
Efficiency
95% Max
Transfer time
0 ms
Protections
Short-circuit, output overload, overtemperature, battery low voltage, overvoltage / undervoltage and fan failure
Max. number of parallel connections
4
Communications
RS232, USB, RS485, EPO, Dry contacts, Parallel port (Standard) SNMP card, WI-FI card, GPRS card, SMS alarms (Optional)
Display
LED + 5 inches LCD touch screen
Operating temperature
0C ~ 40C
Storage temperature
Min 40 C Under Zero ~ 70 B360C (B360without battery)
Relative humidity
0 ~ 95% (non-condensing)
Altitude
<1000m, load derated 1% per 100m from 1000 ~ 2000m
IP rating
IP 20
Noise level at 1 m
58dB 100% load, 55dB 50% load
Dimensions (mm)
250 x 840 x 930

Is expected
Code
0.502.135
Category
Tescom UPS
Rated Voltage
380 / 400 / 415 Vac (L-L)
Voltage range
304~478Vac (L-L), full load 228V~304Vac (L-L), load decrease linearly according to the min phase voltage
Rated frequency
50 / 60 Hz (auto-sensing)
Frequency range
40 ~ 70 Hz
Power factor
> 0.99Total Harmonic Distortion (THDi) <3% (full linear load)
Rated Voltage
380 / 400 / 415 Vac (L-L)
Voltage Regulation
= +- 1% (full linear load)
Frequency
Synchronized with utility in mains mode, 50/60 Hz ±0.1% in battery mode
Waveform
Sinusoidal
Power factor
1
Harmonic Distortion
<1% (full linear load) <3% (full non-linear load according to IEC/EN62040-3)
Current Crest Ratio
3:1
Overload
<110%, 60min, 110%~125%, 10min; 125%~150%,1min, >150%, 200ms
Bypass voltage range
Selectable, default -20%~+15% Up limited: +10%, +15%, +20%, +25%; Down limited: -10%, -15%, -20%, -30%, -40%
Bypass frequency range
Selectable, + - 1Hz, + - 3Hz, + - 5Hz
Bypass overload
125%: long term operation; 125%~130%: 10min; 130%~150%: 1min; 150%~400%: 1s; >400%, less than 200ms
DC voltage
120 ~ 240 Vdc settable
Charging current
10A Max
Recharge time
90% capacity restored in 8 hours
Charger voltage precision
1%
Inbuilt battery
N/A
Efficiency
95% Max
Transfer time
0 ms
Protections
Short-circuit, output overload, overtemperature, battery low voltage, overvoltage / undervoltage and fan failure
Max. number of parallel connections
4
Communications
RS232, USB, RS485, EPO, Dry contacts, Parallel port (Standard) SNMP card, WI-FI card, GPRS card, SMS alarms (Optional)
Display
LED + 5 inches LCD touch screen
Operating temperature
0C ~ 40C
Storage temperature
Min 40 C Under Zero ~ 70 B360C (B360without battery)
Relative humidity
0 ~ 95% (non-condensing)
Altitude
<1000m, load derated 1% per 100m from 1000 ~ 2000m
IP rating
IP 20
Noise level at 1 m
58dB 100% load, 55dB 50% load
Dimensions (mm)
250 x 800 x 700
There are 63 products
Products 1 - 15 of 63
Prices do NOT include VAT
Our Certifications
Why we Stand out
MORE
Microsoft authorized refurbisher
Microsoft surface authorized reseller
ADISA Accredited Pass
BLANCO
WEEE
ISO 27001
ISO 14001
ISO 9001
×

This site uses cookies to distinguish visitors. To accept the use of cookies, please select
Cookies policy